250kW AMICO Natural Gas Genset
Our industrial and commercial gas generator sets are proven for reliable operation with a wide range of gaseous fuels including natural gas, biogas from landfills and digesters, coal gas, propane and alternative fuels. We build durable, low life-cycle cost power systems that we integrate with controls, exhaust systems, fuel train, combined cooling heat & power skids and switchgear.
Contact information
E-mail
E-mail: landy.industry20@gmail.com
We will reply to you within 24 hours.
Recommended Operation Conditions
|
1. CH4 Content of Gas ≥ 76%
|
|
2. Gas Pressure ≥3 kPa
|
|
3. Calorific Value ≥ 32 MJ/m³
|
|
4. H2S Content of Gas ≤ 20 mg/m³
|
|
5. Total Sulphur Content of Gas ≤ 460 mg/m³
|
|
6. Altitude ≤ 4,000 m
|
|
7. -25℃ ≤ Ambient Temperature ≤ +50℃
|
Advantages & Features
|
1. Reliable Steyr & AVL Tech. engine, Mecc Altea alternator and DEIF controller
|
|
2. This 250kW gas generator enjoys advanced lean-burn technology
|
|
3. Prompt dynamic response similar to diesel genset
|
|
4. Excellent power generation efficiency of this home standby generator
|
|
5. This backup generator is adaptable for a wide range of gas pressure
|
|
6. Humanized manual, semi-auto and full-auto operation modes
|
Specification & Configuration
250kW Gas Genset
|
|
Model
|
AMC250GF4-PN
|
|
Prime Power
|
250 kW (312.5 kVA)
|
|
Rated Voltage
|
230/400 V
|
|
Rated Current
|
451 A
|
|
Rated Frequency
|
50 or 60 Hz
|
|
Power Factor
|
0.8
|
|
Gas Consumption
|
0.29 Nm³/kWh
|
|
Weight
|
1,950 kgs
|
|
Overall Size (L × W × H)
|
2,950 × 1,150 × 1,720 mm
|
Engine
|
|
Brand
|
CNHTC (Steyr & AVL Tech.)
|
|
Model
|
T12
|
|
Type
|
6-cylinder, 4-stroke, turbocharged
|
|
Displacement
|
11.596 L
|
|
Compression Ratio
|
11
|
|
Ignition
|
Electric control, independent ignition
|
|
Fuel Control
|
Lean-burn, closed-loop control
|
|
Speed Control
|
Electric control
|
|
Rated Speed
|
1500 rpm
|
|
Conversion Efficiency
|
40%
|
Alternator
|
|
Brand
|
Mecc Altea
|
|
Model
|
ECO38-2LN/4
|
|
Type of Excitation System
|
Brushless with AVR
|
|
Connection Type
|
3-Phase, 4-Line
|
|
Conversion Efficiency
|
93.4%
|
Controller
|
|
Brand
|
DEIF
|
|
Model
|
AGC222
|
|
Type
|
Manual control, semi-auto control or full-auto control
|
Others
|
|
Pedestal, radiator, air filter, muffler, battery and gas pressure reducer are included.
|
|
Soundproof equipment, engine oil, coolant and output cable are not included.
|
All specifications are subject to change without prior notice.
Documents Download